Notifier ID3000 Fire Alarm Panel: The Ultimate Solution for Safety

When it comes to fire safety and alarm systems, you'll find no better option than the Notifier ID3000 Fire Alarm Panel. Built by the reputable manufacturer Notifier by Honeywell, this Fixed 2 Loop Analogue Addressable Panel with SKU 002-474 is a symbol of dependability.

Description of the Product: NOTIFIER ID3000 FIRE ALARM PANEL - FIXED 2 LOOP ANALOGUE ADDRESSABLE - 002-474

The Notifier ID3000 Fire Alarm Panel is a state-of-the-art alarm system that combines innovation and functionality. Its features include a code or keyswitch entry, 16 zones, and the capacity for 99 sensors and 99 input/output modules per loop. Not to mention its LPCB approval and certification to EN54 Parts 2 & 4, ensuring its compliance with the highest safety standards.

Notably, this product's large 240 x 64 pixel LCD screen is clear and easy to navigate. This way, even in times of emergency, you can trust it to deliver prompt and accurate information.

Battery Options for the Alarm Panel

The Notifier ID3000 alarm panel requires 2 x 12Ah 12V Sealed Lead Acid Batteries. These batteries offer long-lasting power that ensures your panel will stay active, even in the event of a power outage. It's always wise to keep spare batteries on hand, which you can conveniently find at Fire Trade Supplies.

Manufacturer Information: Notifier by Honeywell

Notifier by Honeywell has a rich history in delivering cutting-edge fire detection systems. The Notifier ID3000 panel is a testament to their commitment to quality and innovation. The brand's products offer unmatched reliability and performance, making them a top choice for fire safety solutions.

Features of the Notifier ID3000 Fire Alarm Panel

"The only thing necessary for the triumph of fire is for good systems to do nothing." – Adapted from Edmund Burke

  • Fixed 2 Loop Analogue Addressable Panel: The ability to support two loops makes this panel incredibly versatile.
  • Code or Keyswitch Entry: Security is never compromised with the double-layered access.
  • 16 Zones: Divide your property into 16 different areas for comprehensive coverage.
  • 99 Sensor & 99 Input/Output Module Capacity per loop: Maximizing the potential of your fire safety system.
  • Certified to EN54 Parts 2 & 4: Compliance with the highest European standards.
  • LPCB Approved: An assurance of quality and reliability.
  • Large 240 X 64 Pixel LCD Screen: Clear and comprehensive display for user-friendly operation.

Limitations of the Panel

Though highly functional, the Notifier ID3000 panel cannot be extended beyond 2 loops. However, with its capacity to hold up to 99 sensors and 99 input/output modules per loop, it offers more than enough coverage for most buildings.

Purchasing as a Spare/Replacement Part for Existing Notifier Systems

If you're already enjoying the benefits of a Notifier system, the ID3000 panel can be a valuable addition or replacement.

It's fully compatible with other Notifier components like the B501AP Notifier Analogue Addressable Detector Base and NFXI-TFIX58 Notifier Fixed Temp 58 Deg Heat Detector.

Requirement of Commissioning by a Notifier ESD Engineer

For the validity of the warranty, it's important that the system is commissioned by a Notifier ESD engineer. This ensures that all aspects of the panel are operating correctly and safely.

Fire Trade Supplies: Your Trusted Provider

Fire Trade Supplies offers an extensive range of fire and safety products. We pride ourselves on supplying top-tier brands like Notifier by Honeywell, ensuring you have access to the most dependable fire safety solutions. Visit our website today to explore our offerings and secure the safety of your property.

Loop Outputs Output voltage 22.5 to 26.4V Maximum load 0.5A* Loop driver source impedance 3.8 ohms at 22.5V Total system load Limited by the available PSU output. Notifier Loop and Battery Calculator Support Tool should be used to ensure the system is not overloaded RS232 Serial Port (Optional) Isolation Functional at 30V Baud rate Up to 9600 Baud, Software-selectable Connector Terminal block on RS232 PCB Max cable length 15m RS485 Serial Port (Optional) Isolation Functional at 30V Baud rate 1200 Baud Connector Terminal block on RS485 PCB Maximum cable length 3000m (minimum of 1mm² screened cable recommended)

 

*Please note that certain specifications are optional and may not be included in all models of the ID3002 2 Loop Addressable Fire Alarm Control Panel.

🛠Specifications: ID3002 2 Loop Addressable Fire Alarm Control Panel

Category Specification
Mechanical Aspects
Dimensions Height: 400 mm, Width: 500 mm, Depth: 153 mm
Weight 14 kg (excluding batteries)
Environmental Factors
Climatic classification 3K5, in line with IEC 721-2-3
Operating temperature -5°C to +45°C
Relative humidity 5% to 95%, without condensation
Ingress Protection (IP) Rating IP30, compliant with EN 60529
Vibration Matches EN 60068-2-6, 10-150Hz at 0.981ms-2
EMC Emissions Adheres to EN 61000-6-3
EMC Immunity Follows EN 50130-4
Safety Compliant with EN 60950
Electrical Attributes
Supply rating External double-pole mains isolation unit to provide mains supply to the panel, with a capacity of 230V~(ac) ± 15%, 5A, 50Hz ±4%.
PSU3A Output Ratings Output voltage: 26.0Vdc - 28.3Vdc (stabilised), Ripple voltage: ± 300mV, EN54 PSU Loadings Imax(a): 600mA; Imax(b): 3A; I(min): 0A
Outputs
Dedicated Sounder Output Circuits Two
Sounder or Volt-free Contact (VFC) - selectable outputs Two
VFC outputs dedicated to Common Fire and Common Fault Two
Standard outputs Two
24Vdc auxiliary outputs Two
Loop Outputs
Output voltage 22.5 to 26.4V
Maximum load 0.5A*
Loop driver source impedance 3.8 ohms at 22.5V
Total system load Limited by the available PSU output. Notifier Loop and Battery Calculator Support Tool should be used to ensure the system is not overloaded
RS232 Serial Port (Optional)
Isolation Functional at 30V
Baud rate Up to 9600 Baud, Software-selectable
Connector Terminal block on RS232 PCB
Max cable length 15m
RS485 Serial Port (Optional)
Isolation Functional at 30V
Baud rate 1200 Baud
Connector Terminal block on RS485 PCB
Maximum cable length 3000m (minimum of 1mm² screened cable recommended)

*Please note that certain specifications are optional and may not be included in all models of the ID3002 2 Loop Addressable Fire Alarm Control Panel.

 

 